Skip to main navigation Skip to search Skip to main content

Effect of substation grounding on the neutral voltage in substations with multiple independent resonant grounding systems

Ameen Gargoom, Amanullah Oo, Md Enamul Haque, Martin Cavanagh, Jon Bernardo

Research output: Chapter in Book/Report/Conference proceedingConference proceeding contributionpeer-review

Abstract

The paper puts forward a recent practical issue which has never been addressed before that is associated with resonant grounded networks fed from multiple independent transformers and located in the same substation. This situation is common when the network is not initially designed as a resonant grounding network and the intention of using resonant grounding scheme is to reduce the risk of bushfire due to ground faults. In these situations, undesirable over-voltages are noticed on several practical healthy networks when faults occur on other networks. The paper analyses this phenomenon and investigates the factors impacting these unexpected over-voltages to help industries associated with such phenomenon to achieve the best strategies to avoid it.

Original languageEnglish
Title of host publication2018 IEEE Industry Applications Society Annual Meeting (IAS)
Place of PublicationPiscataway, NJ
PublisherInstitute of Electrical and Electronics Engineers (IEEE)
Pages1-7
Number of pages7
ISBN (Electronic)9781538645369, 9781538645352
ISBN (Print)9781538645376
DOIs
Publication statusPublished - 2018
Externally publishedYes
Event2018 IEEE Industry Applications Society Annual Meeting, IAS 2018 - Portland, United States
Duration: 23 Sept 201827 Sept 2018

Publication series

Name
ISSN (Print)0197-2618
ISSN (Electronic)2576-702X

Conference

Conference2018 IEEE Industry Applications Society Annual Meeting, IAS 2018
Country/TerritoryUnited States
CityPortland
Period23/09/1827/09/18