Abstract

Drift loss from cooling towers may transmit Legionnaires' disease. Measurement of drift loss is essential to reducing infection. An indirect method, with an additional sample of circulating water and more rigorous equations, avoids errors due to tracer in the makeup water and surroundings. The international standard for potentiometric titration with silver nitrate allows precise and accurate analysis of chloride ion tracer. This modified chloride balance is easy, practical and accurate for drift loss measurement.

Original languageEnglish
Pages (from-to)132-139
Number of pages8
JournalASHRAE Transactions
Volume100
Issue number1
Publication statusPublished - 1994
Externally publishedYes

Fingerprint

Dive into the research topics of 'Measurement of drift loss from cooling towers'. Together they form a unique fingerprint.