Parametric optimisation of raised-floor data centres to enhance the thermal performance

Babak Fakhim, Steven Armfield, Masud Behnia, Nagarathinam Srinarayana, Atef Badr

Research output: Contribution to journalArticleResearchpeer-review

Abstract

Advancement in IT technology and the increasing demand in the
processing and storage requirements have led to an increase in hardware densities, causing a significant cooling challenge in data centre operation. Extensive energy consumption and operational costs in data centre management are the main concerns that have led many engineers and researchers to develop numerous methods and recommendations to improve the efficiency of the cooling system. Establishing the temperature and airflow
pattern for a typical data centre with hot and cold aisles is essential for the efficient thermal management. In this study, thermal analysis of a raised-floor data centre, using computational fluid dynamics (CFD), is undertaken. Factors
including room layout, CRAC location, percentage opening of perforated tile, air distribution system that contribute to efficient cooling in data centre design were studied. To further understand the capability of each design, five investigations were conducted of separate components of the configuration to observe their individual impacts on the overall data centre performance.
Various design solutions to reduce the energy consumption and cost in the data centre are proposed based on the findings.
LanguageEnglish
Pages197-216
Number of pages20
JournalInternational journal of aerodynamics
Volume6
Issue number2/3/4
DOIs
Publication statusPublished - 2018

Fingerprint

Energy utilization
Cooling
Tile
Cooling systems
Temperature control
Thermoanalysis
Costs
Computational fluid dynamics
Hardware
Engineers
Air
Hot Temperature
Temperature

Keywords

  • data centre
  • cooling
  • under-floor plenum
  • perforated tiles
  • computer room air conditioning
  • CRAC
  • rack
  • computational fluid dynamics
  • CFD

Cite this

Fakhim, Babak ; Armfield, Steven ; Behnia, Masud ; Srinarayana, Nagarathinam ; Badr, Atef. / Parametric optimisation of raised-floor data centres to enhance the thermal performance. In: International journal of aerodynamics. 2018 ; Vol. 6, No. 2/3/4. pp. 197-216.
@article{993f017b73c8478eb146ecb6091359c6,
title = "Parametric optimisation of raised-floor data centres to enhance the thermal performance",
abstract = "Advancement in IT technology and the increasing demand in theprocessing and storage requirements have led to an increase in hardware densities, causing a significant cooling challenge in data centre operation. Extensive energy consumption and operational costs in data centre management are the main concerns that have led many engineers and researchers to develop numerous methods and recommendations to improve the efficiency of the cooling system. Establishing the temperature and airflowpattern for a typical data centre with hot and cold aisles is essential for the efficient thermal management. In this study, thermal analysis of a raised-floor data centre, using computational fluid dynamics (CFD), is undertaken. Factorsincluding room layout, CRAC location, percentage opening of perforated tile, air distribution system that contribute to efficient cooling in data centre design were studied. To further understand the capability of each design, five investigations were conducted of separate components of the configuration to observe their individual impacts on the overall data centre performance.Various design solutions to reduce the energy consumption and cost in the data centre are proposed based on the findings.",
keywords = "data centre, cooling, under-floor plenum, perforated tiles, computer room air conditioning, CRAC, rack, computational fluid dynamics, CFD",
author = "Babak Fakhim and Steven Armfield and Masud Behnia and Nagarathinam Srinarayana and Atef Badr",
year = "2018",
doi = "10.1504/IJAD.2018.094165",
language = "English",
volume = "6",
pages = "197--216",
journal = "International journal of aerodynamics",
issn = "1743-5447",
publisher = "Inderscience Publishers",
number = "2/3/4",

}

Parametric optimisation of raised-floor data centres to enhance the thermal performance. / Fakhim, Babak; Armfield, Steven; Behnia, Masud; Srinarayana, Nagarathinam; Badr, Atef.

In: International journal of aerodynamics, Vol. 6, No. 2/3/4, 2018, p. 197-216.

Research output: Contribution to journalArticleResearchpeer-review

TY - JOUR

T1 - Parametric optimisation of raised-floor data centres to enhance the thermal performance

AU - Fakhim, Babak

AU - Armfield, Steven

AU - Behnia, Masud

AU - Srinarayana, Nagarathinam

AU - Badr, Atef

PY - 2018

Y1 - 2018

N2 - Advancement in IT technology and the increasing demand in theprocessing and storage requirements have led to an increase in hardware densities, causing a significant cooling challenge in data centre operation. Extensive energy consumption and operational costs in data centre management are the main concerns that have led many engineers and researchers to develop numerous methods and recommendations to improve the efficiency of the cooling system. Establishing the temperature and airflowpattern for a typical data centre with hot and cold aisles is essential for the efficient thermal management. In this study, thermal analysis of a raised-floor data centre, using computational fluid dynamics (CFD), is undertaken. Factorsincluding room layout, CRAC location, percentage opening of perforated tile, air distribution system that contribute to efficient cooling in data centre design were studied. To further understand the capability of each design, five investigations were conducted of separate components of the configuration to observe their individual impacts on the overall data centre performance.Various design solutions to reduce the energy consumption and cost in the data centre are proposed based on the findings.

AB - Advancement in IT technology and the increasing demand in theprocessing and storage requirements have led to an increase in hardware densities, causing a significant cooling challenge in data centre operation. Extensive energy consumption and operational costs in data centre management are the main concerns that have led many engineers and researchers to develop numerous methods and recommendations to improve the efficiency of the cooling system. Establishing the temperature and airflowpattern for a typical data centre with hot and cold aisles is essential for the efficient thermal management. In this study, thermal analysis of a raised-floor data centre, using computational fluid dynamics (CFD), is undertaken. Factorsincluding room layout, CRAC location, percentage opening of perforated tile, air distribution system that contribute to efficient cooling in data centre design were studied. To further understand the capability of each design, five investigations were conducted of separate components of the configuration to observe their individual impacts on the overall data centre performance.Various design solutions to reduce the energy consumption and cost in the data centre are proposed based on the findings.

KW - data centre

KW - cooling

KW - under-floor plenum

KW - perforated tiles

KW - computer room air conditioning

KW - CRAC

KW - rack

KW - computational fluid dynamics

KW - CFD

U2 - 10.1504/IJAD.2018.094165

DO - 10.1504/IJAD.2018.094165

M3 - Article

VL - 6

SP - 197

EP - 216

JO - International journal of aerodynamics

T2 - International journal of aerodynamics

JF - International journal of aerodynamics

SN - 1743-5447

IS - 2/3/4

ER -